Nursing home emergency power system compliance (CMS/Medicare-Medicaid)

People died in nursing home blackouts. 73% still aren't prepared.

Summary

An HHS inspector general audit -- launched after fatal power outages at nursing homes during Hurricane Irma, Winter Storm Uri, and Hurricane Ida -- found that an estimated 73% of the nation's 15,115 Medicare- and Medicaid-participating nursing homes have inadequate or unreliable emergency power systems. Auditors visited 100 nursing homes in person; 72 failed. Some were still running generators built in the 1970s.

By Locusta · July 13, 2026

This audit exists because people already died from this exact failure. During Hurricane Irma in 2017, 12 Florida nursing home residents died from extreme heat after their facility lost power with no way to cool the building. During Hurricane Ida in 2021, 7 Louisiana residents died in unsafe conditions after evacuation to an overcrowded warehouse. In between, Winter Storm Uri knocked out power at 118 Texas nursing homes. Those disasters are why 's inspector general set out to check whether nursing homes nationally were prepared for the next one -- the audit doesn't claim the facilities it later sampled are the same ones involved in those specific incidents. What it found: an estimated 73% -- 10,983 of the country's 15,115 Medicare- and Medicaid-participating nursing homes -- have inadequate or unreliable emergency power systems, a category describes as an 'increased risk of injury or death during a power failure,' not a prediction of how many would repeat those specific outcomes.

72 of 100, checked in person

didn't just extrapolate from paperwork. Auditors visited 95 of 100 sampled nursing homes in person between May and July 2024, reviewing generator maintenance logs, testing records, and physical equipment. 72 of the 100 had at least one deficiency -- 119 in total -- spanning three categories: maintenance record-keeping, circuit coverage, and generator age.

Nursing homes nationally with unreliable emergency power
73%
an estimated 10,983 of 15,115 Medicare/Medicaid-participating nursing homes
Deficiency rate in OIG's on-site sample
72 of 100
119 total deficiencies found across maintenance, circuit coverage, and generator age
Sampled generators 50+ years old
6
including units manufactured in 1972 and 1980, still in active use as of 2024 site visits
Nearly 11,000 nursing homes, three ways of being unprepared
OIG's national estimate of nursing homes with each type of emergency-power deficiency
Inadequate generator maintenance
7,967
Inadequate generator circuit coverage
5,869
Generators 40+ years old
1,447
Source: HHS OIG, Report A-02-23-01022, Findings
View data as table
OIG's national estimate, extrapolated from a 100-home sample: 7,967 nursing homes (53%) have inadequate generator maintenance, 5,869 (39%) have generators that don't power all required circuits, and 1,447 (10%) run generators 40 years of age or older. A home can appear in more than one category, so these do not sum to the 10,983-home total.
Inadequate generator maintenance7,967
Inadequate generator circuit coverage5,869
Generators 40+ years old1,447

Missing logs, empty tanks

The single biggest failure mode was paperwork that should have been routine: 42 of 71 maintenance deficiencies were incomplete records -- missing the monthly load tests or weekly inspections federal rules require. Eighteen more nursing homes had generators without enough fuel to run for the industry-recommended 3 days. Nine couldn't document whether their generators met the 10-second switchover requirement to essential systems during a real outage.

Where the paperwork -- and the fuel -- fell short
The 71 generator-maintenance deficiencies OIG found across 53 sampled nursing homes
Incomplete maintenance records
42
Insufficient fuel for 3 days
18
Transfer time not tracked
9
Unsafe generator location
2
Source: HHS OIG, Report A-02-23-01022, Generator Maintenance
View data as table
Of the 71 maintenance-related deficiencies OIG identified at 53 sampled nursing homes, the largest share (42) was incomplete records -- missing monthly load tests, weekly inspections, or annual fuel-quality tests -- followed by 18 cases of generators without enough fuel to run 3 days, the industry-recommended minimum.
Incomplete maintenance records42
Insufficient fuel for 3 days18
Transfer time not tracked9
Unsafe generator location2

Generators older than the residents' grandchildren

Ten sampled nursing homes ran generators 40 years old or older -- 6 of them 50-plus. Auditors photographed working units manufactured in 1972 and 1980. sets no age limit on nursing home generators; industry guidance puts a diesel unit's realistic lifespan at 30 to 40 years. Nursing home officials blamed the maintenance gaps on frequent management and staff turnover, and blamed the circuit-coverage and generator-age problems on a lack of resources.

The fix: a reminder email

's sole recommendation was that share the audit's findings with nursing homes and 'emphasize the importance' of adequate emergency power -- not new inspections, fines, or funding for generator replacement. agreed, pointing to a 2023 memo on backup microgrid systems as its existing guidance. That's on top of an inspection system that already exists: 's own comments note that state survey agencies already conduct on-site life-safety compliance surveys of nursing homes at least every 15.9 months and investigate substantial noncompliance complaints as they arise -- 's recommendation doesn't expand that system, just adds a reminder on top of it.

The takeaway

  • 73% is a statistical estimate built on a real 72%. 's national projection tracks almost exactly with what its 100-home, in-person sample found -- this isn't a soft extrapolation.
  • The failure mode is mostly avoidable. 42 of 71 maintenance deficiencies were incomplete paperwork -- missed load tests and inspections nursing homes are already required to perform.
  • 's fix adds nothing to existing oversight. 's response is limited to a reminder; the report doesn't call for new inspections, funding, or deadlines beyond the on-site life-safety surveys states already conduct roughly every 16 months.

Two of the 71 maintenance-deficiency categories rest on standards softer than a rule: 's 3-day minimum fuel supply is an industry best-practice recommendation, not a federal requirement, and sets no maximum generator age at all -- 's 40-year unreliability threshold is its own judgment call based on industry standards, applied to 18 and 10 of the sampled homes respectively. Federal rules also permit evacuation as a legal alternative to maintaining onsite power during an emergency (though notes evacuation isn't always feasible in a widespread disaster), and the 2 sampled nursing homes with no generator at all weren't cited as noncompliant because they had no rooms requiring electric life-support equipment. 's audit measured compliance with these standards; it did not verify whether any nursing home's power failure during an actual emergency was directly caused by one of these deficiencies. The 15,115-nursing-home population and 100-home sample reflect participation as of September 30, 2023; 's fieldwork ran through February 2026.

Sources(1) ▾
  • HHS Office of Inspector General, Most Nursing Homes Throughout the United States Do Not Have Adequate or Reliable Emergency Power Systems (2026-04-28)National audit (Report No. A-02-23-01022) of emergency power system compliance at a stratified random sample of 100 Medicare/Medicaid-participating nursing homes, with statistically extrapolated national estimates. Fetched directly from oig.hhs.gov and converted with pdftotext -layout; read in full. oig.hhs.gov · original document